How do you set up the VW3A1101 keypad so that you can use the keypad to program the drive?
Resolution:
The VW3A1101 keypad can normally be used to view and modify the drive configuration. If parameters cannot be accessed or changed, verify the drive's access level and check whether a password protection feature has been enabled. Both of these settings can restrict access to configuration parameters.
The procedure for changing the access level varies depending on the drive model. For example, on an ATV61, navigate to:
Main Menu >> 2 Access Level >> Expert
Setting the access level to Expert provides access to all configuration parameters. If parameter access is still restricted after changing the access level, verify that a configuration password has not been applied to the drive.
Also, keep in mind that many parameters cannot be modified while the drive is running. If a parameter is read-only or unavailable, stop the drive and try again.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.