How Do You Program an ATS22 Soft Starter to Trip When the Number of Starts per Hour Is Exceeded?

Resolution:

The ATS22 soft starter allows you to limit the number of motor starts within a defined time period. If the programmed limit is exceeded, the soft starter will trip to protect the equipment.

Resolution / Programming Steps:

  1. Access the Adjustment (Adj) menu on the ATS22.
  2. Set Snb (Number of Starts):
    • Options: Off or 1 to 10 starts
  3. Set SLG (Start Period):
    • Options: 1 to 60 minutes

How It Works (Example):

  • If Snb = 3 and SLG = 10 minutes, the soft starter allows up to 3 starts within 10 minutes.
  • If the motor is started more than 3 times during this period, the ATS22 will trip with a SnbF fault.

This setting helps prevent excessive starting that could overheat or damage the motor.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Attachment(s)
ats22_user_manual_en_bbv51330_02.pdf [3.02 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings