Can you use the ATV12 drive on 230vac single phase input and get 230vac 3 phase output?
Issue:
Using an ATV12 drive on 230vac 1 phase input and getting 230vac 3 phase output.
Product Line:
Altivar 12
Environment:
All
Cause:
Needs to feed the drive 1 phase input and have 3 phase voltage coming out of the drive.
Resolution:
The ATV12 version with suffix M2 is designed for 230vac single phase input and will produce a 230vac 3 phase output.
The ATV12 version with suffix M3 is not designed or rated for single phase supply.
Note that all Altivar drives are designed to control / run 3phase motors. They are not designed for phase converter applications to power a machine that includes various loads such as contactors, transformers, relays, heaters, pilot lights etc...
Using an ATV12 drive on 230vac 1 phase input and getting 230vac 3 phase output.
Product Line:
Altivar 12
Environment:
All
Cause:
Needs to feed the drive 1 phase input and have 3 phase voltage coming out of the drive.
Resolution:
The ATV12 version with suffix M2 is designed for 230vac single phase input and will produce a 230vac 3 phase output.
The ATV12 version with suffix M3 is not designed or rated for single phase supply.
Note that all Altivar drives are designed to control / run 3phase motors. They are not designed for phase converter applications to power a machine that includes various loads such as contactors, transformers, relays, heaters, pilot lights etc...
Released for: Schneider Electric USA
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.