What can cause a short circuit fault on an ATS22?

Issue:
Getting an SCF (Short Circuit Fault) on an ATS22.


Resolution:
There are a number of reasons for a short circuit fault detected on an ATS22 Soft Start:
1.  Megger the motor and motor cables. The motor may have a short circuit in any or all windings phase to phase or phase to ground. The motor wires could be shorted to ground.
2.  SCR's may be shorted, or the internal shorting contactor may be stuck closed. Measure resistance across each phase of the Softstart (L1 to T1, L2 to T2, L3 to T3). Check for, at minimum, 50K Ohms resistance on each phase.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings