How can we help you today?

Will the PK4NVL work with the NQ panelboard?

Issue:
PK4NVL works on a NQ panelboard

Product Line:
Panelboard Vault Lock

Environment:
NQ

Resolution:
The PK4NVL can be used on the NQ panelboard but, strictly with a Nema 3R/12 enclosure.

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.