How can we help you today?

What is the handle force required to operate the handle of a Powerp=PacT P frame breaker?

Issue:
What are the required forces to reset and turn the PowerPacT P frame breaker ON and OFF?

Product Line:
Molded Case Circuit Breaker

Resolution:
For a manually operated, PowerPacT P frame circuit breaker (has a toggle handle), the following are the forces required to operate the handle:
  • ON = 56 pounds (force required to close the breaker by pushing the handle from OFF to ON)
  • OFF = 34 pounds (force required to open the breaker by pushing the handle from ON to OFF)
  • RESET = 70 pounds (force required to reset the breaker after a trip by pushing the handle from TRIPPED to OFF)
NOTE: This does not apply to a breaker with a motor operator.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings