How can we help you today?

Where can I find a instruction bulletin or data sheet on the VZ3V1206, VZ3V1207, VZ3V1208 and VZ3V1211 cooling fan kits?

Issue:
Instruction bulletin or data sheet for VZ3V1206, VZ3V1207, VZ3V1208 and VZ3V1211 cooling fan kits?

Resolution:
See the attached bulletin 30072-452-10



If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Attachment(s)

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.