What can cause an OCL fault on ATV21 or ATV212 drives, and how can it be troubleshot?

Resolution:

An OCL fault indicates an output short-circuit condition. Possible causes include a phase-to-phase short circuit, a problem with the motor or motor cables, or low insulation resistance between the motor circuit and ground.

Follow these steps to help isolate the source of the OCL fault:

  1. Inspect the motor and motor cables

    • Power down the drive and follow the appropriate electrical safety procedures.
    • Disconnect the motor leads from the drive.
    • Inspect the motor and wiring for damaged insulation, loose connections, or evidence of a short circuit.
    • Perform the appropriate insulation-resistance tests on the motor and motor cables to check for phase-to-phase or phase-to-ground insulation problems. Follow the motor manufacturer's recommended test voltage and procedure.
  2. Determine whether the fault is associated with the motor circuit

    • If the motor and cables test correctly, the drive can be tested without the motor connected to help determine whether the OCL fault is coming from the drive.
    • Turn off the drive and wait for the DC bus to fully discharge before disconnecting or working on the output terminals.
    • Set F605 (Output Phase Loss detection) = 0 and F307 = 2 as required for the no-load test.
    • With the motor disconnected, run the drive at approximately 20 Hz, 40 Hz, and 60 Hz.
    • Measure the output voltage at each frequency and verify that the phase-to-phase output voltages are balanced and increase appropriately with frequency.

Safety note: VFD output terminals can contain hazardous voltage. Output-voltage measurements should only be performed by qualified personnel using appropriately rated equipment and the required electrical safety procedures.


If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.