How can we help you today?
How do you go from 3 wire control to 2 wire control on the ATV312 drives?
Issue:
Looking to go from 3 wire control to 2 wire control on the ATV312 drives.
Product Line:
Altivar ATV31 and ATV312 drives
Environment:
All
Cause:
The drive was programmed for 3 wire control and now they want change it to 2 wire control.
Resolution:
Programming changes
Go In to the IO menu enter.
find TCC enter
If TCC is 3 C change it to 2C for 2 wire control,
Please note this is a special parameter you will need to hold enter for 3 to 4 seconds.
Looking to go from 3 wire control to 2 wire control on the ATV312 drives.
Product Line:
Altivar ATV31 and ATV312 drives
Environment:
All
Cause:
The drive was programmed for 3 wire control and now they want change it to 2 wire control.
Resolution:
Programming changes
Go In to the IO menu enter.
find TCC enter
If TCC is 3 C change it to 2C for 2 wire control,
Please note this is a special parameter you will need to hold enter for 3 to 4 seconds.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.