What is E A320 error on a Lexium32 drive?
Issue:
Error A320 is a following error. The load-dependent position deviation (following errror) is the difference between the reference position and the actual position caused by the load.
Cause:
External load or acceleration are too high.
Resolution:
Reduce external load or acceleration. Use a differently rated drive, if necessary. Error response can be adjusted via parameter Error-Resp_p_dif.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.