How can we help you today?

What does Graded Insulation mean in Medium Power Transformers?

Primary side star connected transformers may have a graded insulation on their neutral point in order to optimize the design of the bushing & winding configuration. Due to the electrical characteristic of the neutral point, the Lightning Impulse withstand voltage levels can be graded compared to the primary phases. Thus, we can choose a lower insulated bushing and can design the winding accordingly. This will optimize the overall transformer design. However, this point needs to be agreed with the customer in any case.

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.