Can both sub-feed lugs and thru-feed lugs fit on a main lugs NQ panel ( ie. NQ442L2 ) ?
Issue:
Lugs Product feature
Product Line:
Panelboards
Environment:
NQ
Cause:
Selection
Resolution:
No. A panel can not have SFL and FTL on the same interior as the Neutral will not support it and it has not been tested with UL in that application.