LC1F Mounting Positions

Issue:
What possible mounting positions can the LC1F Contactors be used in without derating?

Product Line:
LC1F contactors - GIC Product
LC1F115 through LC1F2100

Environment:
US Product

Cause:
Product Characteristics

Resolution:
The LC1F contactors can be mounted in a standard vertical orientation with up to a 30 degree incline forward, or they can be rotated 90 degrees counter-clockwise from a standard vertical with no incline forward or backward.  These are the only acceptable mounting positions without derating.  Please see the attached documentation for additional information.

Schneider Electric USA