How can we help you today?
How to program the ATV71 drive to run from local control (keypad)?
Issue:
How to program ATV71 to run from local control?
Product Line:
Altivar 71, ATV71
Environment:
All
Cause:
N/A
Resolution:
Select the Drive menu.
Go to 1.6 Command, menu.
Set Ref 1 channel to HMI.
Set Profile to Not Separate.
How to program ATV71 to run from local control?
Product Line:
Altivar 71, ATV71
Environment:
All
Cause:
N/A
Resolution:
Select the Drive menu.
Go to 1.6 Command, menu.
Set Ref 1 channel to HMI.
Set Profile to Not Separate.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.