How can we help you today?
How Can You Monitor the Remote HMI Stop Button Status on an ATV61/ATV71 Drive?
Resolution:
To monitor the status of the remote HMI Stop button on an ATV61 or ATV71 drive, read Statusword address 8603 (logic address 3201) and check bit 14.
- Bit 14 = 0 → Stop button not pressed
- Bit 14 = 1 → Stop button pressed on the remote HMI (graphic display terminal)
This information is available in the drive Statusword parameter and can be used to detect when the remote HMI Stop button is activated.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.