How can we help you today?
Video: How do I assign an IP address to a Lexium Integrated Drive that supports Ethernet IP?
A demonstration video was created which shows how to assign an IP address using the built-in web page that is available on Lexium Integrated Drives.
The video covers ILS2K , ILE2K and ILA2K devices.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.