Why isn't COM'X 510 quantity scaling working?
Issue
The configured scaling of custom frames of custom devices takes on integer values. For example, if a scale factor of 1.8 is used to convert Fahrenheit to Celsius , it will take on the integer value of 1 and not perform the conversion.
Product Line
COM'X 510
Environment
Custom device custom frames scaling parameter
Resolution
This issue is fixed in firmware V1.1.45.
Note: See KB FA270261 for help upgrading the firmware on a COM'X 510.