How can we help you today?

How to command the Altivar VFD to do a ramp stop via Modbus serial communication?

Article available in these languages:

  • Spanish

Issue:
Altivar VFD ramp stop command via Modbus serial communication

Product Line:
ATV31, ATV312, ATV61, ATV71, ATV58, ATV12, ATV32

Environment:
All serial number

Cause:
N/A

Resolution:
To command the VFD to do a ramp stop, a decimal value of 7 must be written to the command word.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings