How can we help you today?

How to program the ATV212 drive to follow the ACC and DEC set times?

Issue:
Program ATV212 to follow the ACC and DEC set times.

Product Line:
Altivar 212

Environment:
ACC/DEC times

Cause:
N/A

Resolution:
Go into AUF (hit mode).
Arrow down to AU1 and change value from 1 to 0.
Set the ACC and DEC to the desired ramp up and ramp down times.

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.