How can we help you today?
Cannot assign located variable to the Unity Momentum IO
Issue
Cannot assign located variable to the Unity Momentum IO
Product Line
Unity Momentum 171CBU*****
Environment
Unity, Control Expert
Resolution
Located variables cannot be assigned to the Momentum IO as in Concept.
Typically, the hardware configuration information is stored in %KW words for the Unity PLC's. Due to the hardware
limitation, the use of %KW words is not allowed for the Momentum PLC. As a result, Unity is forced to use reserved
%MW words for the module configuration information. The %MW words used for the configuration are intentionally
locked out to prevent the user from changing the values. This also locks out the the use of a %MW assignment for the IO.
Cannot assign located variable to the Unity Momentum IO
Product Line
Unity Momentum 171CBU*****
Environment
Unity, Control Expert
Resolution
Located variables cannot be assigned to the Momentum IO as in Concept.
Typically, the hardware configuration information is stored in %KW words for the Unity PLC's. Due to the hardware
limitation, the use of %KW words is not allowed for the Momentum PLC. As a result, Unity is forced to use reserved
%MW words for the module configuration information. The %MW words used for the configuration are intentionally
locked out to prevent the user from changing the values. This also locks out the the use of a %MW assignment for the IO.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.