How can we help you today?

Does M580 CPU support the CIP service “send RR data”?

Issue

Why is the M580 returning “service not supported “ message?

Product Line

M580, BMENOC

Resolution

M580 supports "Send RR Data" in a successful response to a Forward Open request.

However when configure the M580 as adapter (local slave) to be scanned by a SCADA or Rockwell PLC, the M580 might return a “not supported service” message to the “send RR data” because it doesn’t support Rockwell tags!!

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.