Can I use Altivar Drives with Generator Power?

Resolution:

When using a generator to supply an Altivar drive, the generator must be capable of delivering the required starting current while maintaining voltage and frequency within the tolerances specified in the Altivar catalog.

Consider the following when sizing and configuring the generator:

  • Generator sizing: As a general guideline, a generator rated at approximately 2 times the motor power is typically sufficient.
  • Acceleration and current limit: Generator sizing also depends on the acceleration ramp and the current limitation configured in the Altivar drive. Longer acceleration times and appropriate current limiting may help reduce the required generator capacity.
  • Harmonic currents: The drive can introduce harmonic currents that increase the RMS current in the generator windings and may cause additional heating. Installing a line reactor can help reduce the impact of these harmonics.
  • Generator harmonic capability: Consult the generator manufacturer to determine whether filtering is integrated and to confirm the maximum allowable harmonic distortion.
  • Voltage regulation: The generator's voltage regulation bandwidth should be suitable for drive applications so that it does not react excessively to voltage variations caused by harmonic currents.
  • Optimized sizing: Generator capacity may be reduced from the general recommendation when the application's operating cycles, acceleration requirements, and load profile are well known and are not expected to change.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.