How to set the IO Board Parameters in Scadapack Workbench?

The module_address parameter defines the module address of the sp5607 I/O module.

The address on the module is selected via dip switches on the module. A maximum of eight SCADAPack 5607 I/O type modules may be added to a system

The ain0_type parameter sets the analog input type for analog input channel 1.

There are four input types available.

  • An ain_type of 0 sets the input type to measure 0 to 5V input signals.
  • An ain_type of 1 sets the input type to measure 0 to 10V input signals.
  • An ain_type of 2 sets the input type to measure 0 to 20mA input signals.
  • An ain_type of 3 sets the input type to measure 4 to 20mA input signals.

The ain_filter Parameters:

  • An ain_filter value of 0 sets the input filter for 3Hz and the response time to 155ms at 60Hz and 185ms at 50Hz.
  • An ain_filter value of 1 sets the input filter for 6Hz and the response time to 85ms at 60Hz and 85ms at 50Hz.
  • An ain_filter value of 2 sets the input filter for 11Hz and the response time to 45ms at 60Hz and 55ms at 50Hz.
  • An ain_filter value of 3 sets the input filter for 30Hz and the response time to 30ms at 60Hz and 30ms at 50Hz.

The scan_freq parameter sets the input scan rate for analog inputs. AC noise rejection is improved at the correct frequency. If the module is used in a DC environment, the 60 Hz setting will yield slightly faster response time.

  • A scan_freq value of 0 synchronizes the input scanning to 60Hz.
  • A scan_freq value of 1 synchronizes the input scanning to 50Hz.

The aout_type parameter sets the analog output type for both optional analog output channels.

  • An aout_type value of 0 sets the output type for 0 to 20mA signals.
  • An aout_type value of 1 sets the output type for 4 to 20mA signals.


Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.