How can we have diagnostic information for TMC2*** additional cartridge analog I/O module within a TM221C*** PLC SoMachine/Machine Expert - Basic application program ?
Within TM221C*** PLC and SoMachine/Machine Expert - Basic, we have the possibility to add 1 or 2 optional cartridges (depending on the TM221C*** PLC reference). Such cartridge provides 2 analog inputs or outputs channels as extension for the M221 PLC local I/Os.
For each channel, it exists a dedicated system word object available for diagnostic .
It’s %IWS.0.i for an analog input channel
It’s %QWS.0.i for an analog output channel
With i defined by this way:
i=100 for the 1st channel of the cartridge located 1st slot
i=101 for the 2nd channel of the cartridge located 1st slot
i=200 for the 1st channel of the cartridge located 2nd slot
i=201 for the 2nd channel of the cartridge located 2nd slot
The definition of the code status/diagnostic value is as below:
For %IWS word content definition
| 0 | Normal |
| 1 | Data conversion in progress |
| 2 | Initialization in progress |
| 3 | Input operation setting error or module without input |
| 4 | not used |
| 5 | High limit reached |
| 6 | Low limit reached |
| 7 | Non-volatile memory error |
For %QWS word content definition
| 0 | Normal state |
| 1 | not used |
| 2 | Initialization in progress( after power on) |
| 3 | Output operation setting error or module without output |
| 4 | not used |
| 5 | not used |
| 6 | not used |
| 7 | Non-volatile memory error |
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.