How can we help you today?
Is it possible to use mechanical interlock using cables for source changeover for MTZ/NW/NT breakers inside BlokSeT Switchboard?
Yes it is possible to use the mechanical interlock by cables for MTZ/NW/NT breakers inside the BlokSeT column.
Below is the procedure which needs to be followed to have this solution inside the BlokSeT.
2. Masterpact catalog gives source changeover to assemble in different combinations.
Below is the procedure which needs to be followed to have this solution inside the BlokSeT.
- The U-channel of the column should be cut as shown. The dimension of material to be removed is 200 x 25 as shown below.
2. Masterpact catalog gives source changeover to assemble in different combinations.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.