How can we help you today?
How to change the default counter interrogation time in PSE by using IEC870IP driver
Please add and change the following parameters in the citect.ini, and change the default value to what you need.
[IEC870IP]
CounterPollTimeSec Determines how often a counter interrogation is performed. 0~32767(in second) default value is 1800
CounterPollType Determines the type of counter interrogation message that is sent. 0 – No freeze or reset default value is 1
1 – Freeze without reset
2 – Freeze with reset
3 – Reset only
You can also check the detailed information in the Driver's help.
[IEC870IP]
CounterPollTimeSec Determines how often a counter interrogation is performed. 0~32767(in second) default value is 1800
CounterPollType Determines the type of counter interrogation message that is sent. 0 – No freeze or reset default value is 1
1 – Freeze without reset
2 – Freeze with reset
3 – Reset only
You can also check the detailed information in the Driver's help.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.