How can we help you today?

How to reconfigure the application of 140ERT85420 from S908 RIO to QEIO.

There are some ERT configured in Quantum S908 RIO station. After user upgraded the system from S908 to QEIO, the ERT EFB STATUS is 16#5000 that means Wrong Slot. The health bit of ERT module is "1"(OK).
Check the EFB configuration in the application, Found the issue is the number of Drop configuration error. In S908 system the first Remote IO drop number is 2, but in EIO system the frist default value of drop is 1; so customer is easy to have this error if they copied their application program from a old S908 system.

Change the number of the drop from 2 to 1, the ERT work correctly.
The picture is in attachment

Schneider Electric USA

Attachment(s)
ERT config.jpg [126.53 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings