How can we help you today?

How many wires will the 84 space NQ neutral accept?

Issue:
How many wires will the neutral accept in an NQ 84 circuit panel?

Product Line:
NQ panelboards sold and supported in the USA

Environment:
Installation

Cause:
Application/product features

Resolution:
400A and 600A will accept:
(60) #4 - #14,
(22) #6 - #14
(4) 2/0 - #14.

225A will accept:
(90) #4 - #14

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings