How to enable wire broken function for BMXARTxx
Some user thought the wire broken function is enable as default. It is not indicated the wire status after running. Even though the user manual describe it clearly.
Make sure that enable the wirebroken function in configuration page, and use the READ_STS to update the status in program.
Attachment1: How to enable wire broken function
Attachment2: description in user manual
Make sure that enable the wirebroken function in configuration page, and use the READ_STS to update the status in program.
Attachment1: How to enable wire broken function
Attachment2: description in user manual