What is SCF4 on the ATV32 drive and How Can I Troubleshoot It?

Resolution:
The SCF4 [IGBT Short Circuit] fault indicates that the drive has detected a possible fault in one of its power components, such as the IGBT output stage.

Follow these troubleshooting steps:

1. Perform an IGBT Self-Test

  • Cycle power to the drive.
  • If the fault clears, navigate to the FLT menu.
  • Select IGBT TEST and set Strt = Yes.
  • Ensure the motor is connected to the drive before starting the test.
  • Review and record any test results that do not indicate OK.

2. Test the Drive Without the Motor If:

  • The IGBT test completes successfully, or
  • The SCF4 fault persists after a power cycle,

disconnect the motor and test the drive independently.

Before running this test:

  • Set Motor Control Type (drC menu) to V/F 2pts.
  • Set Output Phase Loss (FLT menu) to No.

Run the drive at several speeds and verify that the output phase-to-phase voltages remain balanced.

Warning: This procedure should only be performed by qualified personnel using appropriate PPE and test equipment, as hazardous voltages may be present.

3. Evaluate the Results

If the SCF4 fault appears immediately at power-up or the drive fails the tests above, an internal power component may be damaged. In this case, the drive may require repair or replacement.


If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings