How can we help you today?
How to Import Logical Device Templates for EM4800 and BCPM in PME 7.2.2 and PME 8.x?
Issue
How to import Logical Device Templates for EM4800 and BCPM into current versions of Power Monitoring Expert.
Product Line
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024
Environment
Logical Device Templates
EM4800
BCPM
Management Console
Cause
The Logical Device Template was created using an older driver source (for example, SPM 7.0.1 or older PME driver sets).
These templates are not directly compatible with newer PME systems because the Logical Device Type definitions and measurement sets differ across versions.
Resolution
To import the Logical Device Template into PME:
-
Identify the origin of the template
- Templates created using SPM 7.0.1 or other legacy driver versions cannot be imported directly into modern PME systems.
-
Create a new Logical Device Type in PME
- Open Management Console.
- Navigate to Tools → Logical Device → Logical Device Type Editor.
-
Define all required measurements
- Review the Logical Device Template’s Output Measurement column (column F).
- Examine any circuit (e.g., Circuit 01 or Circuit 02).
- All circuits use the same measurement set.
-
Build the Logical Device Type
- Add all the measurements supported by each circuit (such as Current, Voltage, energy metrics, etc.).
-
Import the Logical Device Template into PME
- Once the Logical Device Type is created, the template can be imported successfully.
Recommendation:
If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.