What is the minimum motor rating that can be used with an ATS22 soft starter?

Resolution:

The ATS22 soft starter is flexible and can operate motors smaller than its rated size. However, proper configuration is important to ensure reliable operation and protection. The ATS22 provides motor overload protection for motors with a Full Load Amperage (FLA) of at least 40% of the soft starter’s rated current (IcL)The motor current parameter (In) can be set within a range of:
0.4 × IcL to 1 × IcL
If the motor’s FLA is below 40% of the soft starter rating:
  • The internal overload protection may not be sufficient.
  • It is recommended to install an external overload relay for proper motor protection.
Always size the soft starter as close as possible to the motor rating. If oversizing is necessary, ensure additional protection is implemented.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.