How can we help you today?
How to Write a number to 3nnnn register in SCADAPack with TelePACE firmware?
The 30000-class register table is for Input Registers and is read-only to external Modbus masters. If you need a writable target over Modbus, use 40000-class table for Holding Registers.
That being said, you can have TelePACE ladder logic push data into a 3nnnn register if required. Using the OVER function block in TelePACE Studio, a register value can be written into a 3nnnn register . The source register can be any valid 0nnnn (coil register), 1nnnn (status register), 3nnnn (input register) or 4nnnn (holding register)
Please note: Using the OVER block will override the value in the destination input register. This is considered a force in the controller and will turn on the SCADAPack's FORCE LED .
Released for: Schneider Electric USA
Explore more
Product:
Explore more
Product:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.