How can we help you today?
What is the MTTF for the Tesys T Motor Management Relay?
We have the MTTF (Mean time to failure) value for this product. These values are provided by statistics regarding the experience of the product in industrial area.
The MTTF for the product Tesys T is 700 000 hours. This value is done by test and simulation.
The calculated MTTF for various Tesys T part references are provided below and in attachment.
| Surrounding temperature: 60°C | MTTF (in Hours) | ||||||
| Contr. Power Supply | Modbus | Profibus | DeviceNet | CANopen | Ethernet | ||
| LTMR | 24VDC | 881924 | 883203 | 888920 | 888920 | 525956 | |
| 100-240VAC | 862156 | 863377 | 868841 | 868841 | 515916 | ||
| LTMR+LTME | 24VDC | 701682 | 702491 | 706104 | 706104 | 456087 | |
| 100-240VAC | 703945 | 704759 | 708395 | 708395 | 454756 | ||
| Surrounding temperature: 15°C | MTTF (in Hours) | ||||||
| Contr. Power Supply | Modbus | Profibus | DeviceNet | CANopen | Ethernet | ||
| LTMR | 24VDC | 2189252 | 2231027 | 2259601 | 2259601 | 1314890 | |
| 100-240VAC | 2244059 | 2287979 | 2318034 | 2318034 | 1289790 | ||
| LTMR+LTME | 24VDC | 1670071 | 1694272 | 1710700 | 1710700 | 1140217 | |
| 100-240VAC | 1754072 | 1780792 | 1798946 | 1798946 | 1136890 | ||
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.