How can we help you today?
Are there any IO expansions for the Magelis HMISCU HMI controller?
Issue:
Are there any IO expansions for the Magelis HMISCU HMI controller?
Product Line:
HMISCU, HMISCU8B5, HMISCU8A5, HMISCU6B5, HMISCU6A5, IO expansion, I/O expansion
EcoStruxure Machine Expert Software
Resolution:
The HMISCU does not have any IO expansion modules that connect directly to it, however now, there is a TM3 Bus Coupler Module that allows fast connectivity with TM3 I/O Modules.
The CANopen TM3 Bus Coupler - Part Number TM3BCCO connects to the embedded CANopen port on the HMISCU and is added from the Devices Tree under the CAN > CAN_Optimized node:
Underneath the TM3BC_CANopen node, TM3 Digital and Analog I/O Modules can be added:
From there, the TM3 I/O Modules can be configured and symbols can be mapped:
Also see the Catalog for TM3 Expansion IO Modules .
[Legacy Information]
Before the addition of the TM3 Bus Coupler in EcoStruxure Machine Expert, the previous options would have been to use:
- Advantys OTB island
- Advantys STB island
- use a small PLC (M221) with a Magelis (HMISTU) instead of the HMISCU.
- OTB1C0DM9LP - CANopen
- OTB1S0DM9LP - Modbus
- OTB1E0DM9LP - Ethernet MB-TCP/IP
The OTB1C0DM9LP (CANopen) version's configuration software is integrated into SoMachine v3.1 and higher.
What distributed I/O network interface modules are available for Advantys OTB ?
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.