How can we help you today?

Why does an ATV61 or ATV71 drive not respond to commands over Modbus TCP/IP?

Resolution:
A Server IP address may be configured in the drive's Modbus TCP/IP settings. When a Server IP address is assigned, the drive accepts control commands only from the device using that IP address.
If the controlling PLC or Modbus TCP/IP client has a different IP address, the drive may communicate normally but will not accept its command or reference values.

Check the Server IP address configured in the drive.

  • If only one PLC controls the drive, verify that the Server IP address matches the IP address of that PLC.
  • For troubleshooting, temporarily unassign or clear the Server IP address.
  • After clearing the Server IP address, test communication by writing to the drive's command word and speed reference.
  • If the drive responds after the Server IP address is removed, verify the IP address of the intended controller before configuring the Server IP again.

This setting helps ensure that control commands are accepted only from the intended Modbus TCP/IP controller.

Modbus TCP uses Ethernet as a transport layer to deliver a Modbus payload.  You might need to set a Modbus Address on parameter ADD. Even when it is for Modbus Serial, this parameter might need to have a value matching the unit ID in the PLC.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.