In Vijeo Designer, how do we record the date and time to a variable when a button is pressed?
Issue:
How to record a timestamp to a variable when a button is pressed?
Product Line:
Vijeo Designer (all versions)
Resolution:
To record the date and time when a button is pressed, you will need to create a script in that button that copies the system variables _Hours, _Minutes, _Seconds, _Year2, _Month, _Day to a string variable for time and a string variable for date.
Please see the example script below:
//-------------------------------------
//Script Created: Jan 25, 2016
//
// Description:
//
//-------------------------------------
// Replace this line with your script
String YearYY = _Year2.getStringValue();
String MonthMM = _Month.getStringValue();
String DayDD = _Day.getStringValue();
if(_Month.getIntValue() < 10)
{
MonthMM = "0" + _Month.getStringValue();
}
if(_Day.getIntValue() < 10)
{
DayDD = "0" + _Day.getStringValue();
}
DateString.write(YearYY + "/" + MonthMM + "/" + DayDD);
String HoursHH = _Hour.getStringValue();
String MinutesMM = _Minutes.getStringValue();
String SecondsSS = _Seconds.getStringValue();
if(_Seconds.getIntValue() < 10)
{
SecondsSS = "0" + _Seconds.getStringValue();
}
if(_Hour.getIntValue() > 11)
{
temp.write(_Hour.getIntValue() - 12);
HoursHH = temp.getStringValue();
TimeString.write(HoursHH + ":" + MinutesMM + ":" + SecondsSS + " pm");
}
else
{
TimeString.write(HoursHH + ":" + MinutesMM + ":" + SecondsSS + " am");
}
How to record a timestamp to a variable when a button is pressed?
Product Line:
Vijeo Designer (all versions)
Resolution:
To record the date and time when a button is pressed, you will need to create a script in that button that copies the system variables _Hours, _Minutes, _Seconds, _Year2, _Month, _Day to a string variable for time and a string variable for date.
Please see the example script below:
//-------------------------------------
//Script Created: Jan 25, 2016
//
// Description:
//
//-------------------------------------
// Replace this line with your script
String YearYY = _Year2.getStringValue();
String MonthMM = _Month.getStringValue();
String DayDD = _Day.getStringValue();
if(_Month.getIntValue() < 10)
{
MonthMM = "0" + _Month.getStringValue();
}
if(_Day.getIntValue() < 10)
{
DayDD = "0" + _Day.getStringValue();
}
DateString.write(YearYY + "/" + MonthMM + "/" + DayDD);
String HoursHH = _Hour.getStringValue();
String MinutesMM = _Minutes.getStringValue();
String SecondsSS = _Seconds.getStringValue();
if(_Seconds.getIntValue() < 10)
{
SecondsSS = "0" + _Seconds.getStringValue();
}
if(_Hour.getIntValue() > 11)
{
temp.write(_Hour.getIntValue() - 12);
HoursHH = temp.getStringValue();
TimeString.write(HoursHH + ":" + MinutesMM + ":" + SecondsSS + " pm");
}
else
{
TimeString.write(HoursHH + ":" + MinutesMM + ":" + SecondsSS + " am");
}
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.