Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the standard amps per square inch on panelboard bussing?

Article available in these languages: Spanish

Issue:
How is the standard amps on panelboard bussing rated, per square inch , temperature?

Product Line:
Circuit breaker panelboards sold and supported in the USA.

Environment:
Application

Cause:
Specification

Resolution:
Manufacturers have a choice of testing their panels by amps per sq. inch or heat rise.
Schneider chooses to test by the heat rise method as we feel it is a better test of how connections and joints will react based on actual temperatures rather than the sq. in. calculation method.

We don't have an amps per sq. in. rating for our panels. If per square in rating is needed, it would require the selection to High Density Buss option of 750 amps per sq. in. for Aluminum, or 1000 amps per sq. in. for Copper in product selectors.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings