How can we help you today?

What could cause the errors: "Invalid Read Reply" and "Specified Address Invalid" on the Magelis when communicating to the Siemens S7-1200 ethernet driver?

Issue:
What could cause the errors:  "Invalid Read Reply" and "Specified Address Invalid" on the Magelis when communicating to the Siemens S7-1200 ethernet driver?

Product Line:
S7-1211C, S7-1212C, S7-1214C, S7-1215C, S7 ethernet

Resolution:
Protection
From TIA (Siemens programming software), Select the CPU project in the left pane and press Alt-Enter (or in the contextual menu select “Properties…”)
In the item Protection, select “Full access” and Check “Permit access with PUT/GET communications from remote partner” as in figure below.

SIEMENS TIA


Information was taken from:  http://snap7.sourceforge.net/snap7_client.html 2-25-2016

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings