What type of breakers will install in an NQ panelboard?
Issue:
What type of breakers does an NQ panelboard accept?
Product Line:
NQ
Environment:
Panelboards
Cause:
Need to know what type of breakers can be used in a panelboard
Resolution:
NQ panelboards accept QO and QOB branch breakers. These mount directly to the bus; no additional hardware is required. See individual panelboards for amperage restrictions. Tandem breakers cannot be used in an NQ panelboard.
A subfeed Q-frame, H-frame, or J-frame breaker can also be installed. These require a subfeed breaker kit and a larger enclosure.
What type of breakers does an NQ panelboard accept?
Product Line:
NQ
Environment:
Panelboards
Cause:
Need to know what type of breakers can be used in a panelboard
Resolution:
NQ panelboards accept QO and QOB branch breakers. These mount directly to the bus; no additional hardware is required. See individual panelboards for amperage restrictions. Tandem breakers cannot be used in an NQ panelboard.
A subfeed Q-frame, H-frame, or J-frame breaker can also be installed. These require a subfeed breaker kit and a larger enclosure.
Released for: Schneider Electric USA