How can we help you today?

How to manage Data inconsistencies in DDDT type of Advantys equipments used in Unity Pro?

Goals and Symptoms

On some equipment, you can have inconsistencies between data in the DDDT type of Advantys equipment when used in Unity Pro.

Example: STB AHI 8321 Module used in an STB island with STB NIP 2x 1x module.
Image1

Causes and Fixes

This behavior is normal If the data is not 32-bit aligned that means, if the Primary variable (32 bit data) object is not acquiring addresses like 0,4,8,12 etc...then the M580 master aligns them automatically to the Byte array. So it is necessary to plan the island in such a way that the variables falls at a 32-bit boundary.

Another easier solution consists in Configuration Advantys software for each module to add an alignment parameter, this parameter allows to re-align the variables.
Image2

After validation variables become consistent.
Image3


Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.