What is the cable to use to connect the HMIGTO to the Premium PLC on the TER port for Unitelway?
Issue:
What is the cable to use to connect the HMIGTO to the Premium PLC on the TER port for Unitelway?
Product Line:
Magelis HMI (XBTGT, XBTGK, HMISTO, HMISTU, HMIGTO, HMIGTU, XBTGH)
Resolution:
The cable to use would be the XBTZ9780 in order to connect the HMIGTO/XBTGT/HMIGTU/HMISTU/HMISTO to the TSX Premium series PLC via the TER port to communciate over Uni-Telway protocol.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.