What extra width is needed for a Back to Back installation for a Model 6 MCC transition section?

Issue:
Extra width needed for a Back to Back installation for a Model 6 MCC transition section

Product Line:
Model 6 Motor Control Center

Environment:
Layout

Cause:
Space allocation

Resolution:
The additional width needed for bussing transition section is 12", and back to back clearance needs to be 1" apart.
Back-To-Back MCC Top view