How can we help you today?
Video: Why does the Local/Remote button not work on the Process drive keypad?
Issue:
Local/Remote button does not work
Product line:
Altivar 600 Family: ATV630, ATV650, ATV660, ATV680
Altivar 900 Family: ATV930, ATV950, ATV960, ATV980
Environment:
All
Cause:
Default programming
Resolution:
The factory setting for Process drives' Local/Remote button is 'deactivated'.
To activate it:
Stop means that the drive will be stopped when switching between Local and Remote and a new run command will be required.
Local/Remote button does not work
Product line:
Altivar 600 Family: ATV630, ATV650, ATV660, ATV680
Altivar 900 Family: ATV930, ATV950, ATV960, ATV980
Environment:
All
Cause:
Default programming
Resolution:
The factory setting for Process drives' Local/Remote button is 'deactivated'.
To activate it:
- go to menu 5: Complete Settings (CSt-)
- go to menu 5.5 for ATV600: menu 5.4 for ATV900: Command and Reference (CrP)
- go to parameter HMI cmd. (bMP) and change it from Deactivated (diS) to Bumpless (buMP) or to Stop.
Stop means that the drive will be stopped when switching between Local and Remote and a new run command will be required.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.