Video: Why does the Local/Remote button not work on the Process drive keypad?

Issue:
Local/Remote button does not work

Product line:
Altivar 600, ATV630, ATV650, ATV930

Environment:
All

Cause:
Default programming

Resolution:
The factory setting for Process drives' Local/Remote button is 'disabled'.
To activate it, go to menu 5 Complete Settings (CSt-) > menu 5.5 Command and Reference (CrP) > HMI cmd. (bMP) and change it from Disabled (diS) to Bumpless (buMP).