How Do I Change the Motor Control Type on an ATV61 or ATV71 Drive?
Resolution:
To change the Motor Control Type on an ATV61 or ATV71 drive:
- Ensure the drive is powered on and in the RDY (Ready) state with no run command active.
- Press ESC until you return to the Main Menu with Drive Menu highlighted.
- Press ENTER to access the Drive Menu.
- Navigate to Menu 1.4 - Motor Control and press ENTER.
- Scroll to Motor Control Type and press ENTER.
- Select the desired motor control mode from the available options.
- Confirm your selection and exit the menu.
The ATV71 offers additional motor control modes compared to the ATV61, including closed-loop control options when an encoder is used. The available selections may vary depending on the drive model and configuration.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.