How can we help you today?

What is the total DC bus capacitance for the ATV960 drive in microfarads?

Issue:
Needs the total DC bus capacitance for the ATV960  in microfarads

Product Line:
ATV960

Environment:
All

Cause:
N/A

Resolution:
T
he DC capacitance for the ATV660/960 is 10mF per brick.

1p: ATV960C11 ... C16: 10mF
2p: ATV960C20 ... C31: 20mF
3p: ATV960C35 ... C50: 30mF
4p: ATV960C56 ... C63: 40mF
5p; ATV960C71 ... C80: 50mF

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.