Why will my Altivar Drive not accept any program changes?

Issue:
Drive not accepting program changes

Resolution:
Typical reasons that a VFD will not allow a parameter to be changed:
Verify the drive does not have an active run command.  Most parameters changes require the VFD to not be in run status.
Verify the parameter is not incompatible with other parameter settings.
Verify that [AdC] Auto DC Injection is Not set to Ct [Continuous].
Must change AdC to Yes or No to adjust any other parameters which don't permit changes while running..
*Note: Setting ADC to Continuous DC Injection can damage a motor.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings