Does a Sine Wave Filter Affect Torque Measurement on Altivar Drives?

Resolution:
No. Installing a sine wave filter between the drive and the motor does not negatively affect the drive's torque measurement. In many cases, it can actually improve measurement accuracy.

A sine wave filter smooths the drive output current, producing a waveform that is closer to a true sinusoidal signal. Without a sine wave filter, the output current contains switching peaks and harmonics that can reduce current measurement accuracy.

Since motor torque is directly proportional to motor current (Torque ∝ Current), a cleaner current waveform can result in a more accurate torque calculation.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.