How can we help you today?

What wire sizes will fit into the QONK1, 2, 3, or 4 neutral bars?

Issue:
Size of wire accepted

Product Line:
QO Load centers

Resolution:
The QONK1, 2, 3, or 4 will accommodate wire sizes of #4 to #14 Cu, or #4 to #12 Al.
These neutral bars have a 90 °C rating.

Wire Size by Type and Torques
CU Wire RangeAL Wire RangeTorque (in-lbs)
#14 (2 wires)#12 (2 wires)20-35
#12 (2 wires)#10 (2 wires)20-35
#10 (2 wires)#10 (1 wire) &
#12 (1 wire) (Solid or Stranded)
20-35
#12 (1 wire) &
#14 (1 wire) (Solid or Stranded)*
20-35
#10 (1 wire) &
#14 (1 wire) (Solid or Stranded)*
20-35
#10 (1 wire) &
#12 (1 wire) (Solid or Stranded)*
20-35
#10-14 (1 wire)#10-12 (1 wire)20
#8 (1 wire)#8 (1 wire)25
#4-6 (1 wire)#4-6 (1 wire)35

*(Wire of same type )