How can we help you today?

Unity Pro : increasing or decreasing the number of %M or %MW lead to wrong values for %I or %IW,


On Modicon Momentum & M340, with PLC using State Ram: increasing or decreasing the number of %M or %MW lead to wrong values for %I or %IW, after a build change.
A rebuild all is manadatory.

The hotfix UnityPro_V110_ HF0323828R fixes the issue on Unity Pro V11

The hotfix UnityPro_V100_ HF0323828R will fix the issue on Unity Pro V10

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.